What subcooling is and how to measure it

Subcooling is the number of degrees a liquid is below its saturation temperature. It helps assess whether the refrigerant has enough margin to reach the expansion valve as liquid.

  1. Saturation 40 °C
  2. Minus liquid reading 34 °C
  3. Subcooling 6 K

Measure at a representative location

Stabilize the equipment and measure liquid-line temperature with pressure at the same location. A pressure reading from farther away may skew the calculation if there is pressure drop. Use the location specified by the manufacturer.

Subtract in the right order

Convert pressure to saturation temperature. For blends with glide, use the bubble point. Subtract actual liquid temperature from saturation temperature. For example, 40 °C minus 34 °C gives 6 K of subcooling.

Use it as part of the diagnosis

Read it alongside superheat, pressure drop through filters and the liquid line, heat exchanger condition and receiver configuration. In transcritical CO₂ operation above critical pressure at the gas cooler outlet, there is no saturation temperature. Use the parameters specified by the equipment controls.

Guide for trained technicians. Follow the manufacturer’s procedure and limits for the refrigerant and equipment model being serviced.